Power Factor Correction
A capacitor is considered a generator of positive reactive power, and its function in the power system is to supply reactive power needed by inductive loads. It is desirable to operate with loads that are not highly inductive. By compensating such loads with a shunt capacitor, the source current and apparent power decrease, resulting in more efficient operation and better voltage regulation. Also, reduced current permits the use of smaller conductors, so a significant savings in equipment and wiring costs may be realized by keeping power factor close to unity. The practice of improving a lagging power factor by installing capacitors in parallel with an inductive load is called power factor correction.
Example Problem 1:
Draw the power triangle for a single-phase source which delivers 80 kW to a load at 0.7 pf lagging. If the source voltage is 480 V, calculate the current required by this load.
Solution:
- Example Problem Size the shunt capacitor required to reduce the power factor in Example Problem 3 to 0.9 lagging.
- The original load impedance found in Example Problem 1 is
Solution:
This impedance contains resistive and inductive elements:
After power factor correction, load impedance will be
Note that a change in load impedance from
Now, examine the power triangle after power factor correction.
3-Phase Power
The 3-phase (3S3
and for a Delta circuit, the equation is
S3
Another adavantage of having a balanced circuit is that each phase has the same power. That is,
S
so that,
S3
Just in case you didn't know, right now you should be thinking "This is very cool!"
The single phase power can be found using either
S
We can do some interesting rearrangements to get the power in terms of the line voltage (Vab) and line current (Ia) only.
S
Thus, S3
- Note:
- In balanced systems, all the S
's and S3
have the same power factor (pf) and thus the same power factor angle = impedance angle =
.
No comments:
Post a Comment